Illuminator LV – 175VA, 350VA, 550VA, 750VA & 1100VA

Myers EPS offers a line of mini inverters designed for small spaces. These systems support all lamp sources, including LED.

Capacity and Dimensions

  • 175VA/W: 7.50″ H x 23.84″ W x 8.0″ D (Grid)
  • 175VA/W: 19.75″ H x 16.25″ W x 6.5″ D (Wall – Recessed Mount)
  • 175VA/W: 17.75″ H x 14.25″ W x 6.5″ D (Wall – Standard Surface Mount)
  • 350VA/W & 550 VA/W: 22″ H x 19″ W x 9.25″ D
  • 750VA/W: 22″ H x 25.25″ W x 9.25″ D
  • 1100VA/W: 25.3″ H x 26″ W x 10.125″ D

Standard Features

  • High Efficiency System
  • Compatible With Incandescent, Fluorescent, LED & Quartz
  • Input Fuse and Battery Fuse Protection
  • 90 Minute Run Time
  • System Status Indicators & Momentary Test Switch
  • Red Wall Mounted Cabinet
  • High Crest Factor and Inrush Capabilities
  • Pure Sine Wave
  • Summary Fault Dry Form C Contacts
  • NEMA Type 1 Cabinet

Optional Features

  • Enhanced Communications
    • Expanded Building Management Protocols
    • BACnet or Modbus Communications Interface
    • NEW IoT Connect Cloud Software
  • Status Monitoring Contacts
  • Output Circuit Breakers (Except on 175VA/W Systems)
  • Floor Mount
  • Battery Strapping
  • Plenum Rated 175VA Grid Mount Only
  • Automatic Event, Test and Alarm Log
  • NFPA 101 Self Testing and Data Logging
  • Factory Startup and Training
  • OSHPD Rated Units (Contact Factory)

Specifications

  • Input Voltage: Field Selectable at 120VAC or 277VAC; 1-Phase 2-Wire Plus Ground +10% to -15%
  • Relative Humidity < 95% (Non-Condensing)
  • Load Power Factor: 0.5 Lagging to 0.5 Leading
  • Output Voltage Distortion < 10% for Resistive Loads
  • Line Interactive PWM Inverter Type Utilizing MOSFET Technology
  • Compatible With Generators (10x Inverter Size)
  • Maintenance Free VRLA Batteries
  • Microprocessor-Controlled, 3-Stage Battery Charger
  • Alarms Include Monthly Test Fault, Yearly Test Fault, Charger Fault, Load Reduction Fault, Output Voltage Low, Output Voltage High, Overload Fault, Low Voltage Disconnect, Heatsink Over Temp and Input Fuse Failure
  • 10kAIC at 120VAC; 1.5kAIC at 277VAC
  • Inverter Operating Temp. 32°F/0°C to 104°F/40°C
  • Battery Operating Temp. 68°F/20°C to 86°F/30°C per UL 924 Specifications